請(qǐng)相信上海西皇自動(dòng)化科技有限公司是您忠誠(chéng)的長(zhǎng)久的合作伙伴,我們?cè)概c廣大客戶攜手向前,共同進(jìn)步!
數(shù)字量輸出模塊具有下列機(jī)械特性:
具有8、16、32或64通道的模塊。
數(shù)字量輸出模塊將控制器的內(nèi)部信號(hào)電平(邏輯“0”或“1”)轉(zhuǎn)換成過(guò)程所需的外部信號(hào)電平。
多種輸出電壓,可支持輸出不同的過(guò)程信號(hào):
除了經(jīng)濟(jì)性以及易于處理的特點(diǎn)外,該模塊還具有其他特殊功能:
Order number |
6AG1322-1BF01-2XB0 |
6AG1322-8BF00-2AB0 |
6AG1322-1BH01-2AA0 |
6AG1322-1BL00-2AA0 |
|
---|---|---|---|---|---|
SIPLUS S7-300 SM322 |
SIPLUS SM322 8DA/24VDC |
SIPLUS SM322 16DA/24VDC |
SIPLUS S7-300 DIGITALAUSGABE SM322 |
||
Supply voltage |
|
|
|
|
|
Load voltage L+ |
|
|
|
|
|
|
24 V |
24 V |
24 V |
24 V |
|
Input current |
|
|
|
|
|
from load voltage L+ (without load), max. |
60 mA |
90 mA |
80 mA |
160 mA |
|
from backplane bus 5 V DC, max. |
40 mA |
70 mA |
80 mA |
110 mA |
|
Power loss |
|
|
|
|
|
Power loss, typ. |
6.8 W |
5 W |
4.9 W |
6.6 W |
|
Digital outputs |
|
|
|
|
|
Number of digital outputs |
8 |
8 |
16 |
32 |
|
Limitation of inductive shutdown voltage to |
L+ (-48 V) |
L+ (-45 V) |
L+ (-53 V) |
L+ (-53 V) |
|
Switching capacity of the outputs |
|
|
|
|
|
|
10 W |
5 W |
5 W |
5 W |
|
Load resistance range |
|
|
|
|
|
|
12 Ω |
48 Ω |
48 Ω |
48 Ω |
|
|
4 kΩ |
3 kΩ |
4 kΩ |
4 kΩ |
|
Output voltage |
|
|
|
|
|
|
L+ (-0.8 V) |
L+ (-0.8 to -1.6 V) |
L+ (-0.8 V) |
L+ (-0.8 V) |
|
Output current |
|
|
|
|
|
|
2 A |
0.5 A |
0.5 A |
0.5 A |
|
|
5 mA |
10 mA |
5 mA |
5 mA |
|
|
2.4 A |
0.6 A |
0.6 A |
0.6 A |
|
|
5 mA |
10 mA |
5 mA |
5 mA |
|
|
2.4 A |
0.6 A |
0.6 A |
0.6 A |
|
|
5 mA |
10 mA |
5 mA |
5 mA |
|
|
0.5 mA |
0.5 mA |
0.5 mA |
0.5 mA |
|
Switching frequency |
|
|
|
|
|
|
100 Hz |
100 Hz |
100 Hz |
100 Hz |
|
|
0.5 Hz |
2 Hz |
0.5 Hz |
||
|
10 Hz |
10 Hz |
10 Hz |
10 Hz |
|
Total current of the outputs (per group) |
|
|
|
|
|
horizontal installation |
|
|
|
|
|
|
4 A |
4 A |
4 A |
||
|
4 A |
3 A |
3 A |
3 A |
|
|
4 A |
2.5 A; (without diode) & 1.5 A (with diode) |
3 A |
2 A |
|
vertical installation |
|
|
|
|
|
|
4 A |
4 A |
2 A |
2 A |
|
Cable length |
|
|
|
|
|
|
1 000 m |
1 000 m |
1 000 m |
1 000 m |
|
|
600 m |
600 m |
600 m |
600 m |
|
Interrupts/diagnostics/status inbation |
|
|
|
|
|
Diagnostic functions |
No |
Yes; Parameterizable |
No |
No |
|
Alarms |
|
|
|
|
|
|
No |
Yes; Parameterizable |
No |
No |
|
Potential separation |
|
|
|
|
|
Potential separation digital outputs |
|
|
|
|
|
|
Yes |
Yes |
Yes |
||
|
4 |
8 |
8 |
8 |
|
|
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
Yes; Optocoupler |
|
Isolation |
|
|
|
|
|
Isolation tested with |
500 V DC |
500 V DC |
500 V DC |
500 V DC |
|
Standards, approvals, certificates |
|
|
|
|
|
CE mark |
Yes |
Yes |
Yes |
Yes |
|
UL approval |
Yes; File E239877 |
Yes; File E239877 |
Yes; File E239877 |
Yes; File E239877 |
|
FM approval |
Yes |
Yes; CofC 3028431 |
Yes; CofC 3028431 |
Yes; CofC 3028431 |
|
RCM (berly C-TICK) |
Yes |
Yes |
Yes |
||
KC approval |
Yes |
Yes |
Yes |
||
EAC (berly Gost-R) |
Yes |
Yes |
Yes |
||
Railway application |
|
|
|
|
|
|
No |
||||
|
No |
Yes; T1 Category 1 Class A/B horizontal mounting b |
Yes; T1 Category 1 Class A/B horizontal mounting b |
Yes; T1 Category 1 Class A/B horizontal mounting b |
|
Ambient conditions |
|
|
|
|
|
Ambient temperature during operation |
|
|
|
|
|
|
-25 °C |
-25 °C; = Tmin |
-25 °C |
-25 °C; = Tmin |
|
|
70 °C; = Tmax; 60 °C @ UL/cUL use |
70 °C; = Tmax; 60 °C @ UL/cUL use |
70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies |
70 °C; = Tmax; for use on railway vehicles according to EN50155, the rated temperature range -25 ... +55 °C (T1) or 60 °C @ UL/ULhaz/ATEX/FM use applies |
|
Ambient temperature during storage/transportation |
|
|
|
|
|
|
-40 °C |
-40 °C |
-40 °C |
||
|
70 °C |
70 °C |
70 °C |
||
Extended ambient conditions |
|
|
|
|
|
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
|
Relative humidity |
|
|
|
|
|
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
|
Resistance |
|
|
|
|
|
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
|
|
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
|
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
|
Connection b |
|
|
|
|
|
required front connector |
20-pin |
20-pin |
20-pin |
40-pin |
|
Dimensions |
|
|
|
|
|
Width |
40 mm |
40 mm |
40 mm |
40 mm |
|
Height |
125 mm |
125 mm |
125 mm |
125 mm |
|
Depth |
120 mm |
120 mm |
120 mm |
120 mm |
|
Weights |
|
|
|
|
|
Weight, approx. |
190 g |
210 g |
190 g |
260 g |
Order number |
6AG1322-1CF00-7AA0 |
6AG1322-1HF10-2AA0 |
6AG1322-5HF00-4AB0 |
6AG1322-1FF01-7AA0 |
|
---|---|---|---|---|---|
SIPLUS SM322 8DA/48-125VDC |
SIPLUS SM322 8DA - Relais |
SIPLUS_SM322_8RO |
SIPLUS S7-300 SM322 8DA/120/220VAC |
||
Supply voltage |
|
|
|
|
|
Load voltage L+ |
|
|
|
|
|
|
48 V; 48 V DC to 125 V DC |
120 V |
24 V |
||
Load voltage L1 |
|
|
|
|
|
|
230 V |
230 V |
230 V; 120/230V AC |
||
Input current |
|
|
|
|
|
from supply voltage L+, max. |
125 mA |
160 mA |
|||
from load voltage L+ (without load), max. |
2 mA |
||||
from load voltage L1 (without load), max. |
2 mA |
||||
from backplane bus 5 V DC, max. |
100 mA |
40 mA |
100 mA |
100 mA |
|
Power loss |
|
|
|
|
|
Power loss, typ. |
7.2 W |
4.2 W |
3.5 W |
8.6 W |
|
Digital outputs |
|
|
|
|
|
Number of digital outputs |
8 |
8; Relays |
8; Relays |
8 |
|
Limitation of inductive shutdown voltage to |
M (-1 V) |
||||
Switching capacity of the outputs |
|
|
|
|
|
|
15 W; 15 W (48 V) or 40 W (125 V) |
1 500 W; 230 V AC |
1 500 W; 230 V AC |
50 W |
|
Output voltage |
|
|
|
|
|
|
L+ (-1.2 V) |
L1 (-1.5 V) |
|||
Output current |
|
|
|
|
|
|
1.5 A |
5 A |
5 A |
2 A |
|
|
10 mA |
10 mA |
|||
|
1.5 A |
2 A |
|||
|
10 mA |
10 mA |
|||
|
1.5 A |
1 A |
|||
|
10 mA |
5 mA |
10 mA |
10 mA |
|
|
3 A; for 10 ms |
20 A; max. 1 AC cycle |
|||
|
0.5 mA |
2 mA |
|||
Switching frequency |
|
|
|
|
|
|
25 Hz |
2 Hz |
2 Hz |
10 Hz |
|
|
0.5 Hz |
0.5 Hz |
0.5 Hz |
0.5 Hz |
|
|
10 Hz |
2 Hz |
2 Hz |
1 Hz |
|
|
10 Hz |
10 Hz |
|||
Total current of the outputs (per group) |
|
|
|
|
|
horizontal installation |
|
|
|
|
|
|
6 A |
4 A |
|||
|
3 A |
5 A |
5 A |
2 A |
|
|
1 A |
5 A |
1.5 A |
||
vertical installation |
|
|
|
|
|
|
4 A |
5 A |
5 A |
2 A |