西門子CPU1211C可編程控制器
西門子CPU1211C可編程控制器
安裝海拔高度 |
不同環(huán)境溫度下的電流降容系數 |
|||||||
---|---|---|---|---|---|---|---|---|
m |
20 °C |
25 °C |
30 °C |
35 °C |
40 °C |
45 °C |
50 °C |
55 °C |
0 ... 2000 |
100% |
100% |
100% |
100% |
100% |
93.3% |
86.7% |
80% |
2001 ... 2500 |
100% |
100% |
100% |
100% |
96.3% |
|
|
|
2501 ... 3000 |
100% |
100% |
100% |
98.7% |
|
|
|
|
3001 ... 3500 |
100% |
100% |
100% |
|
|
|
|
|
3501 ... 4000 |
100% |
100% |
96.3% |
|
|
|
|
|
4001 ... 4500 |
100% |
97.5% |
|
|
|
|
|
|
4501 ... 5000 |
98.2% |
|
|
|
|
|
|
|
取決于脈沖頻率的電流降額
為了降低電機噪聲或提高輸出頻率,可相對于出廠設定值(1.25 kHz 或 2 kHz)來提高脈沖頻率。如果脈沖頻率增加,則必須考慮輸出電流的降容系數。必須將此降額系數應用于技術數據中規(guī)定的電流。
有關詳細資料,請參閱《SINAMICS 低壓工程手冊》。
具有額定脈沖頻率 2 kHz之裝置的輸出電流降額系數(取決于脈沖頻率)
訂貨號 |
類型等級 |
輸出電流 2 kHz 下 |
脈沖頻率的降額因子 |
||||
---|---|---|---|---|---|---|---|
6SL3310-... |
kW |
A |
2.5 kHz |
4 kHz |
5 kHz |
7.5 kHz |
8 kHz |
380 ... 480 V 3 AC |
|||||||
1GE32-1AA3 |
110 |
210 |
95% |
82% |
74% |
54% |
50% |
1GE32-6AA3 |
132 |
260 |
95% |
83% |
74% |
54% |
50% |
1GE33-1AA3 |
160 |
310 |
97% |
88% |
78% |
54% |
50% |
1GE33-8AA3 |
200 |
380 |
96% |
87% |
77% |
54% |
50% |
1GE35-0AA3 |
250 |
490 |
94% |
78% |
71% |
53% |
50% |
具有額定脈沖頻率 1.25 kHz之裝置的輸出電流降額系數(取決于脈沖頻率)
訂貨號 |
類型等級 |
輸出電流 1.25 kHz 下 |
脈沖頻率的降額因子 |
||||
---|---|---|---|---|---|---|---|
6SL3310-... |
kW |
A |
2 kHz |
2.5 kHz |
4 kHz |
5 kHz |
7.5 kHz |
380 ... 480 V 3 AC |
|||||||
1GE36-1AA3 |
315 |
605 |
83% |
72% |
64% |
60% |
40% |
1GE37-5AA3 |
400 |
745 |
83% |
72% |
64% |
60% |
40% |
1GE38-4AA3 |
450 |
840 |
87% |
79% |
64% |
55% |
40% |
1GE41-0AA3 |
560 |
985 |
92% |
87% |
70% |
60% |
50% |
500 ... 600 V 3 AC |
|||||||
1GF31-8AA3 |
110 |
175 |
92% |
87% |
70% |
60% |
40% |
1GF32-2AA3 |
132 |
215 |
92% |
87% |
70% |
60% |
40% |
1GF32-6AA3 |
160 |
260 |
92% |
88% |
71% |
60% |
40% |
1GF33-3AA3 |
200 |
330 |
89% |
82% |
65% |
55% |
40% |
1GF34-1AA3 |
250 |
410 |
89% |
82% |
65% |
55% |
35% |
1GF34-7AA3 |
315 |
465 |
92% |
87% |
67% |
55% |
35% |
1GF35-8AA3 |
400 |
575 |
91% |
85% |
64% |
50% |
30% |
1GF37-4AA3 |
500 |
735 |
87% |
79% |
64% |
55% |
35% |
1GF38-1AA3 |
560 |
810 |
83% |
72% |
61% |
55% |
35% |
660 ... 690 V 3 AC |
|||||||
1GH28-5AA3 |
75 |
85 |
93% |
89% |
71% |
60% |
40% |
1GH31-0AA3 |
90 |
100 |
92% |
88% |
71% |
60% |
40% |
1GH31-2AA3 |
110 |
120 |
92% |
88% |
71% |
60% |
40% |
1GH31-5AA3 |
132 |
150 |
90% |
84% |
66% |
55% |
35% |
1GH31-8AA3 |
160 |
175 |
92% |
87% |
70% |
60% |
40% |
1GH32-2AA3 |
200 |
215 |
92% |
87% |
70% |
60% |
40% |
1GH32-6AA3 |
250 |
260 |
92% |
88% |
71% |
60% |
40% |
1GH33-3AA3 |
315 |
330 |
89% |
82% |
65% |
55% |
40% |
1GH34-1AA3 |
400 |
410 |
89% |
82% |
65% |
55% |
35% |
1GH34-7AA3 |
450 |
465 |
92% |
87% |
67% |
55% |
35% |
1GH35-8AA3 |
560 |
575 |
91% |
85% |
64% |
50% |
35% |
1GH37-4AA3 |
710 |
735 |
87% |
79% |
64% |
55% |
35% |
1GH38-1AA3 |
800 |
810 |
83% |
72% |
61% |
55% |
35% |
注:
通過直線插補,可以確定介于固定值之間的范圍內的脈沖頻率降額因子。
例如,SINAMICS G130 調速柜具有用于克服起步轉矩的過載容量。如果存在更大的峰值負載,那么必須在組態(tài)時考慮這種情況。因此,在具有過載要求的驅動器中,必須將合適的基本負載電流用作所需負荷的基礎。
過載的標準是:在過載發(fā)生前后,變頻調速器以基準負載電流工作,負載的周期為 300s。
基于負載電流低負荷 IL,允許 110 % 的過載 60 s 或 150 % 用于 10 s。
基于負載電流高負荷 IH,允許 150 % 的過載 60 s 或 160 % 用于 10 s。
低過載