新型BVR4平方太陽(yáng)能光伏接地線
配電系統(tǒng)的接地部分(1)相線(L)。輸送電能的導(dǎo)體,正常情況下不接地。(2)中性線(N)。與系統(tǒng)中性點(diǎn)相連,并能起輸送電能作用的導(dǎo)體。(3)保護(hù)中性線(PEN)。兼有保護(hù)線和中性線作用的導(dǎo)體。(4)電源接地點(diǎn)。將電源可以接地的一點(diǎn)(通常是中性點(diǎn))進(jìn)行接地 。
根據(jù)中性線與保護(hù)線是否合并的情況,TN系統(tǒng)又分為T(mén)N-C、TN-S及TN-C-S系統(tǒng)。 TN-C系統(tǒng):保護(hù)線與中性線合并為PEN線。 TN-S系統(tǒng):保護(hù)線與中性線分開(kāi)。 TN-C-S系統(tǒng):在靠近電源側(cè)一段的保護(hù)線和中性線合并為PEN線,從某點(diǎn)以后分為保護(hù)線和中性線。
雙色接地線 黃綠接地線就是直接連接地球的線,也可以稱(chēng)為安全回路線,危險(xiǎn)時(shí)它就把高壓直接轉(zhuǎn)嫁給地球,算是一根生命線。
懸掛點(diǎn)如有接地點(diǎn),應(yīng)用接地線夾或?qū)S勉~棒作接地連接;如無(wú)固定接地點(diǎn)可利用;則可用臨時(shí)接地點(diǎn),接地極埋入地下深度應(yīng)不小于0.6m。
根據(jù)要求方便掛短路接地選擇型的夾具。選擇接地桿操作應(yīng)該工作在和諧與懸點(diǎn)系統(tǒng),額定電壓,懸掛應(yīng)保證員工當(dāng)短路接地,接地和電氣設(shè)備必要的安全距離。在前面的架接地工作結(jié)束后的員工應(yīng)保持接地導(dǎo)體保持安全距離。使用類(lèi)型與短路接地、經(jīng)驗(yàn)確認(rèn)已經(jīng)停電、設(shè)備再?zèng)]有電壓。接地夾連接到互聯(lián)網(wǎng)第一,然后操作桿分別線端端子夾。接地短路接地維護(hù):類(lèi)型與短路接地應(yīng)在空氣流通、干燥的環(huán)境中特殊的沉積位置,應(yīng)仔細(xì)檢查每次使用之前。發(fā)現(xiàn)夾子開(kāi)裂、松散連接、護(hù)套損壞、銅線裸露應(yīng)禁止使用
接地方式 :光伏電站接地系統(tǒng)通常有兩大類(lèi):一是防雷接地,二是工作接地。不同類(lèi)型的接地,要求也不盡相同。防雷接地的接地電阻值一般在4-30歐,而工作接地的接地電阻一般在0.5-10歐。光伏電站占地面積雖大但布局空間有限,為了滿足接地電阻的要求,往往采用全站共用接地系統(tǒng)的設(shè)計(jì)方案。
rest. “This makes it evident to me,” he wrote to the King, “that Lord Robert’s
在電力系統(tǒng)中接地線:是為了在已停電的設(shè)備和線路上意外地出現(xiàn)電壓時(shí)保證工作人員的重要工具。按部頒規(guī)定,接地線必須是以上裸銅軟線制成。
接地線的接地方式的基本組成接地方式的組成部分可分為電氣設(shè)備和配電系統(tǒng)兩部分。
公司配備了高壓局放檢測(cè)裝備,拉力試驗(yàn)機(jī),低溫彎曲試驗(yàn)機(jī),燃燒試驗(yàn)儀,絕緣電阻測(cè)試儀,電子分析天平,故障定位儀等全套檢測(cè)設(shè)備,對(duì)出廠產(chǎn)品嚴(yán)格測(cè)試,我公司生產(chǎn)的光伏接地線,產(chǎn)品型號(hào)齊全,質(zhì)量保證!采用BVR黃綠雙色線制作,發(fā)貨快 價(jià)格優(yōu),本廠接地線全部為國(guó)標(biāo)線,默認(rèn)孔徑5MM,可定制任意孔徑和長(zhǎng)度,請(qǐng)用戶(hù)放心訂購(gòu).我廠自己生產(chǎn)的BVR黃綠雙色線,全部按GB生產(chǎn)。
工作接地方式主要有以下三種類(lèi)型:(1)中性點(diǎn)非直接接地方式(I-T)。用電設(shè)備中性點(diǎn)不接入大地,(2)單個(gè)保護(hù)接地方式(T-T)。電源變壓器的中性點(diǎn)直接接地,用電設(shè)備外殼可導(dǎo)電部分直接接入大地(3)中性點(diǎn)直接接地方式(T-N)。在這種方式中,電力系統(tǒng)變壓器中性點(diǎn)直接接地,用電設(shè)備外殼可導(dǎo)電部分通過(guò)接地引下線和接地系統(tǒng)作良好的金屬性連接,。
but, withal, Guzman did not believe in the sincerity of the new Austrian negotiations, which he looked upon as a “mere diversion,” and, after his conversation with Leicester, wrote: “Lord Robert is more confident now and said ... he could not contemplate the Queen’s marriage with any one but himself without great repugnance.” It is probable that at this time the Queen seriously leant again towards a marriage with Leicester. The proals for a match with the French king were never anything but a feint, with the bs which he been mentioned, and the new negotiations with the Archduke were undertaken, not only to disarm Spain at the Bayonne meetings, but also to b the ground and deceive Cecil,91 Sus, and Norfolk, by an apparently s
我國(guó)配電系統(tǒng)的接地方式已使用IEC規(guī)定,其分類(lèi)仍然是以配電系統(tǒng)和電氣設(shè)備的接地組合來(lái)分,一般分為T(mén)N、TT、IT系統(tǒng)等。上述字母表示的含義:第一個(gè)字母表示電源接地點(diǎn)對(duì)地的關(guān)系。其中T表示直接接地;I表示不接地或通過(guò)阻抗接地。第二個(gè)字母表示電氣設(shè)備的外露可導(dǎo)電部分與地關(guān)系。其中T表示與電源接地點(diǎn)無(wú)連接的單獨(dú)直接接地;N表示直接與電源系統(tǒng)接地點(diǎn)或與該點(diǎn)引出的導(dǎo)體連接。
太陽(yáng)能光伏發(fā)電系統(tǒng)防雷接地方案從光伏建筑一體化發(fā)電系統(tǒng)的結(jié)構(gòu)來(lái)分析,雷電入侵太陽(yáng)能光伏發(fā)電系統(tǒng)主要通過(guò)以下四個(gè)途徑:(1)直擊雷:雷電直接擊中太陽(yáng)能光伏發(fā)電系統(tǒng)的電池方陣,破壞電池板。(2)地電位反擊:雷電擊中外部防雷裝置時(shí),在接地裝置附近產(chǎn)生的過(guò)電壓,通過(guò)接地線對(duì)靠近它的電子設(shè)備的高電位反擊,入侵電壓可高達(dá)數(shù)萬(wàn)伏。(3)太陽(yáng)能電池板的靜電感應(yīng):帶電荷的云對(duì)地面放電時(shí),整個(gè)光伏方陣像一個(gè)大型環(huán)型天線一樣感應(yīng)出上萬(wàn)伏的過(guò)電壓,通過(guò)直流輸入線路引入,擊壞與線路相連的光伏系統(tǒng)設(shè)備。(4)閃電電涌侵入輸出供電線路:供電設(shè)備及供電線路遭受雷擊時(shí),在電源線上出現(xiàn)的雷電過(guò)電壓平均可達(dá)上萬(wàn)伏,雷電電磁脈沖沿電源線浸入光伏微電子設(shè)備及系統(tǒng),可對(duì)系統(tǒng)設(shè)備造成毀滅性的打擊。