Input
|
|
Input
|
1-phase AC
|
Supply voltage
|
|
|
120 V
|
|
230 V
|
|
Automatic range selection
|
Input voltage
|
|
|
85 ... 132 V
|
|
176 ... 264 V
|
Wide-range b
|
No
|
Overvoltage resistance
|
2.3 × Vin rated, 1.3 ms
|
Mains buffering at Iout rated, min.
|
20 ms; at Vin = 93/187 V
|
Rated line frequency 1
|
50 Hz
|
Rated line frequency 2
|
60 Hz
|
Rated line range
|
47 ... 63 Hz
|
Input current
|
|
|
1.2 A
|
|
0.67 A
|
Switch-on current limiting (+25 °C), max.
|
13 A
|
Duration of inrush current limiting at 25 °C
|
|
|
3 ms
|
I²t, max.
|
0.5 A²·s
|
Built-in incoming fuse
|
T 3,15 A/250 V (not accessible)
|
Protection in the mains power b (IEC 898)
|
Recommended miniature circuit breaker: 16 A characteristic B or 10 A characteristic C
|
Output
|
|
Output
|
Controlled, isolated DC voltage
|
Rated voltage Vout DC
|
24 V
|
Total tolerance, static ±
|
3 %
|
Static mains compensation, approx.
|
0.1 %
|
Static load balancing, approx.
|
0.2 %
|
Residual ripple peak-peak, max.
|
150 mV
|
Spikes peak-peak, max. (bandb: 20 MHz)
|
240 mV
|
Product function Output voltage adjustable
|
No
|
Output voltage setting
|
-
|
Status display
|
Green LED for 24 V OK
|
On/off behavior
|
No overshoot of Vout (soft start)
|
Startup delay, max.
|
6 s; 2 s at 230 V, 6 s at 120 V
|
Voltage rise, typ.
|
10 ms
|
Rated current value Iout rated
|
2.5 A
|
Current range
|
0 ... 2.5 A
|
Supplied active power typical
|
60 W
|
Short-term overload current
|
|
|
6 A
|
|
6 A
|
Duration of overloading capability for excess current
|
|
|
100 ms
|
|
100 ms
|
Parallel switching for enhanced perbance
|
Yes
|
Numbers of parallel switchable units for enhanced perbance
|
2
|
Efficiency
|
|
Efficiency at Vout rated, Iout rated, approx.
|
83 %
|
Power loss at Vout rated, Iout rated, approx.
|
12 W
|
Closed-loop control
|
|
Dynamic mains compensation (Vin rated ±15 %), max.
|
0.3 %
|
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ.
|
3 %
|
Load step setting time 50 to 100%, typ.
|
5 ms
|
Load step setting time 100 to 50%, typ.
|
5 ms
|
Setting time maximum
|
5 ms
|
Protection and monitoring
|
|
Output overvoltage protection
|
< 33 V
|
Current limitation, typ.
|
2.65 A
|
Property of the output Short-circuit proof
|
Yes
|
Short-circuit protection
|
Constant current characteristic
|
Enduring short circuit current RMS value
|
|
|
2.7 A
|
Overload/short-circuit indicator
|
-
|
Safety
|
|
Primary/secondary isolation
|
Yes
|
Galvanic isolation
|
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
|
Protection class
|
Class I
|
Leakage current
|
|
|
3.5 mA
|
CE mark
|
Yes
|
UL/cUL (CSA) approval
|
cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cURus-Recognized (UL 60950-1, CSA C22.2 No. 60950-1) File E151273
|
Explosion protection
|
ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455
|
FM approval
|
Class I, Div. 2, Group ABCD, T4
|
CB approval
|
Yes
|
Marine approval
|
GL, ABS, BV, DNV, LRS, NK
|
Degree of protection (EN 60529)
|
IP20
|
EMC
|
|
Emitted interference
|
EN 55022 Class B
|
Supply harmonics limitation
|
not applicable
|
Noise immunity
|
EN 61000-6-2
|
Operating data
|
|
Ambient temperature
|
|
|
0 ... 60 °C
|
|
with natural convection
|
|
-40 ... +85 °C
|
|
-40 ... +85 °C
|
Humidity class according to EN 60721
|
Climate class 3K3, no condensation
|
Mechanics
|
|
Connection technology
|
screw-type terminals
|
Connections
|
|
|
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
|
|
L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
|
|
-
|
Width of the enclosure
|
70 mm
|
Height of the enclosure
|
100 mm
|
Depth of the enclosure
|
75 mm
|
Required spacing
|
|
|
20 mm
|
|
20 mm
|
|
0 mm
|
|
0 mm
|
Weight, approx.
|
0.3 kg
|
Product feature of the enclosure housing for side-by-side mounting
|
Yes
|
Installation
|
Snaps onto DIN rail EN 60715 35x7.5/15, wall mounting
|
MTBF at 40 °C
|
1 492 537 h
|
Other inbation
|
Specifications at rated b voltage and ambient temperature +25 °C (unless otherwise specified)
|